WindO/I-NV4 User’s Manual
3-117
7 BACnet Communication
3
Co
m
m
un
ica
tio
n
Allocate device addresses to Present_Value
Configure the parameters in the
Present_Value Settings
dialog box.
■
Device for Present_Value
Configures the device address for reading Present_Value and the device address for writing Present_Value.
The device address for reading Present_Value and writing Present_Value are automatically assigned according to the
configured device address and
Conversion type
. Starting from the specified address number of Device Address, 2 or
4 continuous words of address number are used.
■
Top device for priority and trigger
Use this device address when writing the value of the device addresses to Present_Value. For details, refer to
Present_Value in “Analog Value Object” on page 3-138.
Device for priority and Device for write trigger are automatically assigned when the device address is set. Starting
from the specified address number of Device Address, 2 continuous words of address number are used.
*1 Specify the priority between 1 and 16. If the priority is out of range, nothing is executed even when the value of Device for
write trigger changes from 0 to 1.
Device for Present_Value
Conversion type
Storage Destination
Present_Value for reading
UBIN16(W), BIN16(I)
The address number of Top Device 0
UBIN32(D), BIN32(L), Float32(F)
The address number of Top Device 0,
The address number of Top Device 1
Present_Value for writing
UBIN16(W), BIN16(I)
The address number of Top Device 1
UBIN32(D), BIN32(L), Float32(F)
The address number of Top Device 2,
The address number of Top Device 3
Specify the Top Device Address so that the address number of device address is not exceeded.
MICRO/I
Storage Destination
Description
Device for
priority
The address number of
Top Device 0
Bit 15:
0: the value of the Present_Value for writing.
1: NULL(00h).
Bits 14 to 5: Disabled
Bits 4 to 0:
Priority
Device for
write trigger
The address number of
Top Device 1
When the value changes from 0 to 1, writes a value to Priority_Array of index
number indicated by the priority (bit 4 to 0 of Device for priority). The value to
be written varies based on the value of bit 15 of Device for priority.
Specify the Top Device Address so that the address number of device address is not exceeded.
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...