WindO/I-NV4 User’s Manual
3-127
7 BACnet Communication
3
Co
m
m
un
ica
tio
n
●
Analog Value Object
This object can be used in the same manner as the Analog Input object and Analog Output object.
Properties List
(1): Read and write from BACnet devices
(2): Read and write from device addresses when properties are allocated to device addresses
R: Read-only, W: Write-only, R/W: Read and write, -: Not Read and write
*1 Character encoding is ISO 10646 (UTF-8), and the maximum size is 64 bytes.
*2 Cannot be displayed on WindO/I-NV4.
Property Identifier
Data Type of Property
(1)
(2)
Comments
Object_Identifier
BACnetObjectIdentifier
R
-
Set a fixed value with WindO/I-NV4.
Object_Name
Character string
R
-
Set a fixed value with WindO/I-NV4.
Object_Type
BACnetObjectType
R
-
Set a fixed value with WindO/I-NV4.
Present_Value
Real number
R
R
Refer to “Present_Value” on page 3-132.
Description
Character string
R
-
Set a fixed value with WindO/I-NV4.
Status_Flags
BACnetStatus_Flags
R
R
Refer to “Status_Flags” on page 3-145.
Event_State
BACnetEventState
R
-
Normal (fixed).
Reliability
BACnetReliability
R
R/W Indicates whether or not Present_Value is
reliable.
Out_Of_Service
Logical value
R/W R/W Refer to “Out_Of_Service” on page 3-146.
Units
BACnetEngineeringUnits
R/W
-
Set the initial value with WindO/I-NV4.
Priority_Array
BACnetPriority_Array
R/W R/W Refer to “Priority_Array” on page 3-145.
Relinquish_Default
Real number
R/W
-
Refer to “Relinquish_Default” on page 3-145.
COV_Increment
Real number
R/W
-
Refer to “COV_Increment” on page 3-145.
Resolution
Real number
R
-
Set a fixed value with WindO/I-NV4.
Property_List
BACnetARRAY[N] of type
BACnetPropertyIdentifier
R
-
Cannot be edited with WindO/I-NV4.
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...