WindO/I-NV4 User’s Manual
12-5
1 Bit Write Command
12
Co
m
m
an
ds
■
Destination Device Address
Specify the destination bit device.
Click
to display the Tag Editor. For the device address configuration procedure, refer to Chapter 2 “5.1 Device
Address Settings” on page 2-70.
■
Write
Specify the number of bit devices (1 to 64) at the destination.
This setting is enabled only if
Action Mode
is set to
Set
or
Reset
.
Example:
This fills a contiguous block of bit devices with the same value.
If the bit number in a word device is specified, the same value is written to same bit of contiguous word devices.
■
Source Data
Specifies the device address where the data to be written is stored.
This setting is enabled only if
Action Mode
is set to
Move
.
Example:
This button writes the values in a contiguous block of bit devices to a contiguous block of device
addresses at the destination.
*1 Advanced mode only
Toggle:
Toggles the value of the specified bit device when the trigger condition is satisfied.
If the value of the bit device is 0 it changes to 1, and vice versa.
Move:
This function writes the value in the source bit device to the value in the destination bit device when
the trigger condition is satisfied.
State of condition
Action
Toggle
Toggle
Condition
Condition
Condition
Condition
Satisfied
Satisfied
Satisfied
Not satisfied
Not satisfied
Not satisfied
Satisfied
Satisfied
Satisfied
Not satisfied
Not satisfied
Not satisfied
State of condition
Action
Move
Move
Condition
Condition
Condition
Condition
Satisfied
Satisfied
Satisfied
Not satisfied
Not satisfied
Not satisfied
Satisfied
Satisfied
Satisfied
Not satisfied
Not satisfied
Not satisfied
1
M0
1
M1
1
M2
1
M3
1
M4
Action Mode: Set
Write: 5
Destination Device Address: M0
Condition
Satisfied
Satisfied
Satisfied
Condition
bit
bit
15
0
Satisfied
Satisfied
Satisfied
1
D0
D1
D2
D3
D4
1
1
1
1
Action Mode: Set
Write: 5
Destination Device Address: D0-15
Device Address: Specify the source bit device.
Click
to display the Tag Editor. For the device address configuration procedure, refer to Chapter
2 “5.1 Device Address Settings” on page 2-70.
Transfer:
Specify the number of bit devices (1 to 64) to move.
1
LM0
0
LM1
0
LM2
1
LM3
Device Address: LM0
Transfer: 4
Destination Device Address: M0
1
M0
0
M1
0
M2
1
M3
Condition
Satisfied
Satisfied
Satisfied
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...