(C) IDM ENERGIESYSTEME GMBH
4. Programming
Technical manaul EIB/KNX
12
D I E
E N E R G I E F A M I L I E
Programming
Pr
ogr
ammi
e
rung
Object
Data
type
Access
Designation
Navigator
parameter
Min.
value
Max.
value
Default-
value
Unit
*266
9
RW
Set room temperature cooling normal HC C
HCC50
15
30
23
[°C]
*267
9
RW
Set room temperature cooling normal HC D
HCD50
15
30
23
[°C]
*268
9
RW
Set room temperature cooling normal HC E
HCE50
15
30
23
[°C]
*269
9
RW
Set room temperature cooling normal HC F
HCF50
15
30
23
[°C]
*270
9
RW
Set room temperature cooling normal HC G
HCG50
15
30
23
[°C]
*271
9
RW
Set room temperature cooling eco HC A
HCA51
15
30
25
[°C]
*272
9
RW
Set room temperature cooling eco HC B
HCB51
15
30
25
[°C]
*273
9
RW
Set room temperature cooling eco HC C
HCC51
15
30
25
[°C]
*274
9
RW
Set room temperature cooling eco HC D
HCD51
15
30
25
[°C]
*275
9
RW
Set room temperature cooling eco HC E
HCE51
15
30
25
[°C]
*276
9
RW
Set room temperature cooling eco HC F
HCF51
15
30
25
[°C]
*277
9
RW
Set room temperature cooling eco HC G
HCG51
15
30
25
[°C]
*278
7
RW
Cooling limit HC A
HCA58
0
36
25
[°C]
*279
7
RW
Cooling limit HC B
HCB58
0
36
25
[°C]
*280
7
RW
Cooling limit HC C
HCC58
0
36
25
[°C]
*281
7
RW
Cooling limit HC D
HCD58
0
36
25
[°C]
*282
7
RW
Cooling limit HC E
HCE58
0
36
25
[°C]
*283
7
RW
Cooling limit HC F
HCF58
0
36
25
[°C]
*284
7
RW
Cooling limit HC G
HCG58
0
36
25
[°C]
*285
7
RW
Set flow temperature cooling HC A
HCA53
8
30
18
[°C]
*286
7
RW
Set flow temperature cooling HC B
HCB53
8
30
18
[°C]
*287
7
RW
Set flow temperature cooling HC C
HCC53
8
30
18
[°C]
*288
7
RW
Set flow temperature cooling HC D
HCD53
8
30
18
[°C]
*289
7
RW
Set flow temperature cooling HC E
HCE53
8
30
18
[°C]
*290
7
RW
Set flow temperature cooling HC F
HCF53
8
30
18
[°C]
*291
7
RW
Set flow temperature cooling HC G
HCG53
8
30
18
[°C]
350
9
W
External room temperature HC A
ZERTA
15
30
[°C]
351
9
W
External room temperature HC B
ZERTB
15
30
[°C]
352
9
W
External room temperature HC C
ZERTC
15
30
[°C]
353
9
W
External room temperature HC D
ZERTD
15
30
[°C]
354
9
W
External room temperature HC E
ZERTE
15
30
[°C]
355
9
W
External room temperature HC F
ZERTF
15
30
[°C]
356
9
W
External room temperature HC G
ZERTG
15
30
[°C]
370
9
W
External outdoor temperature
ZEOT1
[°C]
371
9
W
External humidity
ZEHS1
0
100
[%rF]
*372
7
RW
External requested heating temperature
PH003
20
65
40
[°C]
*373
7
RW
External requested cooling temperature
PC004
10
25
18
[°C]
380
1
RW
Demand heating
ZEBRH
0
1
0