(C) IDM ENERGIESYSTEME GMBH
Technical manaul EIB/KNX
13
D I E
E N E R G I E F A M I L I E
Programmierung
Pr
ogr
ammi
e
rung
Object
Data
type
Access
Designation
Navigator
parameter
Min.
value
Max.
value
Default-
value
Unit
381
1
RW
Demand cooling
ZEBRC
0
1
0
382
1
RW
Demand domestic hot water
ZEBRF
0
1
0
0 ... Off
1 ... On
400
14
RO
Heat quantity heating
kWh
401
14
RO
Heat quantity cooling
kWh
402
14
RO
Heat quantity hot water
kWh
403
14
RO
Heat quantity defrosting
kWh
404
14
RO
Heat quantity passive cooling
kWh
405
14
RO
Heat quantity solar
kWh
406
14
RO
Heat quantity heating immerser
kWh
420
9
RO
Instanteneous power
kW
421
9
RO
Instanteneous power solar
kW
450
9
RO
Solar collector temperature (B73)
[°C]
451
9
RO
Solar collector return temperature (B75)
[°C]
452
9
RO
Solar loading temperature (B74)
[°C]
*453
7
RW
Operation mode solar
0
4
0
0 ... Automatik
1 ... Hot water
2 ... Heating
3 ... Hot water + heating
4 ... Heat source / pool
454
9
RO
Solar heat source - reference temperature/Pool temperature (B76)
[°C]
460
9
RO
ISC loading temperature cooling (B44)
[°C]
461
9
RO
ISC recooling temperature (B49)
[°C]
462
7
RO
ISC mode
0
8
0 ... No waste heat
1 ... heating
4 ... Hot water
8 ... Heat source
499
7
W
Quit error message
ERQALL
Navigator Pro - single room control
500
7
RO
Zone module 1 mode heating/cooling
A14
ZM1
0
1
0 ... Cooling
1 ... Heating
501
7
RO
Zone module 1 dehumidification A12
ZE1
0
1
0
0 ... Off
1 ... On
502
9
RW/RO Zone module 1room temperature zone 1
RT1-1
15
30
[°C]
RW ... Usage of external room sensors
RO ... Usage of IDM room sensors
503
9
RW
Zone module 1 set room temperature zone 1
RS1-1
[°C]