(C) IDM ENERGIESYSTEME GMBH
4. Programming
Technical manaul EIB/KNX
14
D I E
E N E R G I E F A M I L I E
Programming
Pr
ogr
ammi
e
rung
Object
Data
type
Access
Designation
Navigator
parameter
Min.
value
Max.
value
Default-
value
Unit
100 + set temp. = eco-temperature heating; e.g. 120,5 --> eco-temp. heating 20,5°C
200 + set temp. = normal-temperature heating; e.g. 221,5 --> normal-temp. heating 21,5°C
300 + set temp. = comfort-temperature heating; e.g. 323 --> comfort-temp. heating 23°C
400 + set temp. = eco-temperature cooling; e.g. 425,5 --> eco-temp. cooling 25,5°C
500 + set temp. = normal-temperature cooling; e.g. 523 --> normal-temp. cooling 23°C
600 + set temp. = comfort-temperature cooling; e.g. 622 --> comfort-temp. cooling 22°C
Desired temperatures can be set in 0.5 steps within the temperature limits! e.g.: The normal temperature must
be between the eco und comfort temperature.
504
7
RW/RO zone module 1 rroom humidity zone 1
RF1-1
0
100
[%rF]
RW ... Usage of external room sensors
RO ... Usage of IDM room sensors
505
7
RW
Zone module 1 operation mode zone 1
RM1-1
0
4
0 ... Off
1 ... Automatic
2 ... Eco
3 ... Normal
4 ... Comfort
506
7
RO
Zone module 1 status zone 1 (A1)
RR1-1
0
1
0 ... Off
1 ... On
507
9
RW/RO Zone module 1 room temperature zone 2
RT1-2
15
30
[°C]
508
9
RW
Zone module 1 set room temperature zone 2
RS1-2
[°C]
509
7
RW/RO Zone module 1 room humidity zone 2
RF1-2
0
100
[%rF]
510
7
RW
Zone module 1 operation mode zone 2
RM1-2
0
4
511
7
RO
Zone module 1 status zone 2 (A2)
RR1-2
0
1
512
9
RW/RO Zone module 1 room temperature zone 3
RT1-3
15
30
[°C]
513
9
RW
Zone module 1 set room temperature zone 3
RS1-3
[°C]
514
7
RW/RO Zone module 1 room humidity zone 3
RF1-3
0
100
[%rF]
515
7
RW
Zone module 1 operation mode zone 3
RM1-3
0
4
516
7
RO
Zone module 1 status zone 3 (A3)
RR1-3
0
1
517
9
RW/RO Zone module 1 room temperature zone 4
RT1-4
15
30
[°C]
518
9
RW
Zone module 1 set room temperature zone 4
RS1-4
[°C]
519
7
RW/RO Zone module 1 room humidity zone 4
RF1-4
0
100
[%rF]
520
7
RW
Zone module 1 operation mode zone 4
RM1-4
0
4
521
7
RO
Zone module 1 status zone 4 (A4)
RR1-4
0
1
522
9
RW/RO Zone module 1 room temperature zone 5
RT1-5
15
30
[°C]
523
9
RW
Zone module 1 set room temperature zone 5
RS1-5
[°C]
524
7
RW/RO Zone module 1 room humidity zone 5
RF1-5
0
100
[%rF]
525
7
RW
Zone module 1 operation mode zone 5
RM1-5
0
4
526
7
RO
Zone module 1 status zone 5 (A5)
RR1-5
0
1
527
9
RW/RO Zone module 1 room temperature zone 6
RT1-6
15
30
[°C]
528
9
RW
Zone module 1 set room temperature zone 6
RS1-6
[°C]
529
7
RW/RO Zone module 1 room humidity zone 6
RF1-6
0
100
[%rF]