(C) IDM ENERGIESYSTEME GMBH
Technical manaul EIB/KNX
9
D I E
E N E R G I E F A M I L I E
Programmierung
Pr
ogr
ammi
e
rung
NAVIGATOR - EIB/KNX communication
Version: 25.08.2017
Softwareversion Navigator control : since
mod20.3-0
Object
Data
type
Access
Designation
Navigator
parameter
Min.
value
Max.
value
Default-
value
Unit
1
9
RO
External temperature (B31)
[°C]
2
9
RO
Averaged external temperature
[°C]
3
7
RO
Current error code
4
5
RW
System operating mode
SYSMODE
-1
5
1
-1 ... Off
0 ... Standby
1 ... Automatic
2 ... Absent
3 ... Holiday
4 ... Only hot water
5 ... Only heating
5
7
RO
Smart Grid Status
0
4
0 ... Utility lock and no PV current
1 ... Current from utility provider and no PV current
2 ... No current from utility provider and PV current
4 ... Utility lock and PV current
6
9
RO
Heat accumulator (B38)
[°C]
7
9
RO
Cold reservoir (B40)
[°C]
8
9
RO
DHW sensor bottom (B41)
[°C]
9
9
RO
DHW sensor top (B48)
[°C]
20
9
RO
Fresh water temperature (B42)
[°C]
*21
7
RW
Desired hot water temperature
FW030
35
95
46
[°C]
30
9
RO
Heat pump flow temperature (B33)
[°C]
31
9
RO
Heat pump return temperature (B34)
[°C]
32
9
RO
HGL Flow temperature (B35)
[°C]
33
9
RO
Heat source inlet temperature (B43)
[°C]
34
9
RO
Heat source outlet temperature (B36)
[°C]
35
9
RO
Air inlet sensor (B37)
[°C]
36
9
RO
Evaporater (heat exchanger) sensor (B72)
[°C]
50
7
RO
Heat pump operating mode
0
8
0 ... Off
1 ... Heating
2 ... Cooling
4 ... Priority
8 ... Defrosting
60
7
RO
Status compressor 1
0
1
0 ... Off
1 ... On
61
7
RO
Status compressor 2
0
1