ID GATE 6000 Electromechanical Tripod Turnstile
11
Figure 5. ACS control element
—
normally open relay contact
Figure 6. ACS control element
—
circuit with open-collector output
The relays PASS A (contacts
PASS A
and
Common
),
PASS B
(contacts
PASS B
and
Common
),
Ready
(contacts
Ready
and
Common
),
Detector
(contacts
Det Out
and
Common
) and
Alarm
(contacts
Alarm 1
and
Alarm 2
) have normally open contacts. The
“
Common
” contact,
at that, is not connected to the CLB power supply negative terminal.
In the initial (inactive) state, when the power is on, the relay contacts
“
PASS A
”
,
“
PASS B
”,
“
Ready
”
and
“
Detector
”
are closed (voltage is supplied to the relay coil) and the
“
Alarm
”
relay contacts are broken (voltage is not supplied to the relay coil).
The CLB relay operation/release is indicated by lighting up/going down of the red test
indicators located near the corresponding relays (Fig. 4).
The output cascades for
PASS A
,
PASS B
,
Ready
,
Det Out
and
Alarm
are the contacts
with the following signal characteristics (Fig. 7):
maximum commutation voltage...................................................................... 42V DC
maximum switched current................................................................................ 0.25A
closed contact resistance ...................................................... no more than 0.15 Ohm
Figure 7. Output cascades for PASS A, PASS B, Ready, Det Out and Alarm