ACT-457A Panel PC
Page 28
CAUTION:
1. Digital input
A. The system includes a digital input power source
B. Digital input must be less than 50 VDC
2. Relay output
A. Do not exceed maximum contact capacity, limits listed below
240 VAC @ 10 A
120 VAC @ 12 A
28 VDC @ 10 A
B. Total current consumed by peripherals must be < 1 A
C. Relay signal can affect digital input signal, space cables apart
D. Do not connect peripherals with unknown specifications
E. Do not connect unrated/untested external power supplies
The digital I/O port connects to door sensors and alarms. To connect the wires from the
sensor or alarm to the ACT-457A, follow the directions below.
Step 1:
Strip 5 mm of cable housing from the end of the cable.
Step 2:
Loosen the screw.
Step 3:
Position the cable.
Step 4:
Tighten the screw to hold the cable in place.
Step 0:
Summary of Contents for ACT-457A
Page 9: ...ACT 457A Panel PC Page 1 Chapter 1 1 Introduction...
Page 18: ...ACT 457A Panel PC Page 10 Figure 1 9 Front Dimensions...
Page 19: ...ACT 457A Panel PC Page 11 Figure 1 10 Cutout Dimensions...
Page 20: ...ACT 457A Panel PC Page 12 Chapter 2 2 Installation...
Page 37: ...ACT 457A Panel PC Page 29 Figure 2 17 Digital I O Cable Installation...
Page 38: ...ACT 457A Panel PC Page 30 Chapter 3 3 RFID Reader...
Page 49: ...ACT 457A Panel PC Page 41 Chapter 4 4 System Maintenance...
Page 53: ...ACT 457A Panel PC Page 45 Appendix A A External Connector Pinouts...
Page 57: ...ACT 457A Panel PC Page 49 Appendix B B Terminology...
Page 61: ...ACT 457A Panel PC Page 53 Appendix C C Watchdog Timer...
Page 64: ...ACT 457A Panel PC Page 56 Appendix D D Hazardous Materials Disclosure...