The circuit breaker is equipped with a combined release (thermal and 

electromagnetic).

*ATTENTION

When using the circuit breaker in a group B environment, special devices 

should be used to protect against unwanted electromagnetic 

interference.

Degree of protection of the circuit breaker case is IP30 in accordance with 

IEC 60529, of terminals for connecting external conductors – IP00.

The circuit breaker is intended for use in an environment with pollution 

degree 3 according to IEC 60947-1 (conductive pollution is possible or dry, non-
conductive pollution that becomes conductive due to expected condensation).

Specifications

The electromagnetic short-circuit current release should cause the circuit 

breaker opening with an error of ±20

 

% from the operating current value of the 

current setting in accordance with table 2.

Additional assembly units for the switch, ordered separately, are shown in 

table 4.

The overall and installation dimensions of the switch are shown in figure 1.
The bus sizes of the adapter connections for the switch are shown in figure 2. 

The minimum installation distances of the switch are shown in figure 7.

The scope of delivery is shown in table 5.

The circuit diagram of the circuit breaker is shown in figure 6.

The circuit breaker is installed on a metal panel with a thickness of at least 

1.5 mm or an insulating panel with a thickness of at least 6 mm and fixed with the 
screws included in the delivery.

The time-current characteristics of the switch are shown in figure 5.

Setting temperature of the release – plus 40 

°

C. The technical parameters of 

the circuit breakers, depending on the type, are given in table 2. Figure 1 shows the 
graph of the dependence of the rated current value on the ambient temperature.

The thermal release operates with an inverse time delay and must open the 

circuit breaker with an error of ±10 % from operating current value of the IR 
thermal release setting in accordance with table 3.

For the switch, you can additionally purchase extended terminals and 

adapter tips.  The dimensions of the extended terminals and adapter tips for the 
V88 are shown in figure 3. The adapter tips are designated as, "For the central 
terminal" and represent three straight copper busbars. The extended terminals 
consist of one central and two side buses.

Completeness

The connection of the corresponding flexible conductors or busbars is 

carried out using the fasteners for connecting the external conductors. 

Installation rules

The releases are adjusted and calibrated at the factory and are not 

accessible during operation.

K

ARA

T

Summary of Contents for BA88-31

Page 1: ...17516 1 IEC 60947 2 50 40 90 20 IP30 14254 IEC 60529 IP00 2000 5000 1 004 2011 037 2016 IEC 60947 2 IEC 60947 7 3 3 15150 40 60 88 MASTER IEK 30 690 50 IEC 60947 1 A B 3 IEC 60947 1 1 88 MASTER RU KAR...

Page 2: ...2 10 IR 3 4 1 20 2 5 2 7 88 3 5 1 5 6 40 C 2 4 6 5 6 7 6 7 9 13983 KARAT...

Page 3: ...3 10434 17441 1 3 5 1 3 5 90 1 3 5 2 4 6 23216 4 2 15150 8 10 40 C 60 C KARAT...

Page 4: ...aker can be operated under the following conditions operating temperature range from minus 40 to plus 60 environment condition group according to IEC 60947 1 A B utilization category according to IEC...

Page 5: ...uit diagram of the circuit breaker is shown in figure 6 The circuit breaker is installed on a metal panel with a thickness of at least 1 5 mm or an insulating panel with a thickness of at least 6 mm a...

Page 6: ...fer to a specialized recycling company Basic insulation is a precautionary measure for basic protection against electric shock and no protection against damage is provided Transportation of the circui...

Page 7: ...arameter denomination Value Base altitude m 2000 3000 4000 5000 Correction factor of operating current 1 0 94 0 88 0 83 Table 2 Parameter denomination Value for circuit breaker of following type 88 31...

Page 8: ...8 8 8 10 10 Weight kg maximum 0 78 1 4 1 71 5 48 9 9 Continuation of table 2 Table 3 Test current Tripping or non tripping time depending on the setting of thermal releases Requited result I 63 R I 63...

Page 9: ...nductors set 1 1 1 1 1 Fasteners for mounting on a mounting plate set 1 1 1 1 1 Denomination 88 31 88 32 88 35 88 37 88 40 Mounting plate of plug in type 1 125 1 250 1 400 630 1 630 800 Mechanical int...

Page 10: ...7 35 24 35 98 69 4 5 88 37 257 465 224 194 150 48 33 44 150 99 8 88 40 281 496 243 243 210 70 45 70 155 103 7 1 Figure 1 Overall and mounting dimensions of circuit breakers b a L D1 D2 W H c a For cen...

Page 11: ...the rated current on the ambient temperature Rated current Environmental temperature C 0 25 0 25 32 125 88 31 88 32 88 35 Rated current Environmental temperature C Rated current Environmental temperat...

Page 12: ...ng time sec 88 35 Time current characteristics of A88 35 circuit breakers Operating time sec 88 37 Time current characteristics of A88 37 circuit breakers Operating time sec 88 40 ime current characte...

Page 13: ...agnetic release B C H H H 1 3 2 1 Non insulated connection 2 Insulated cable 3 Cable lugs D KARAT Minimum distance between the centers of two horizontally mounted switches Minimum distance of installa...

Page 14: ...ion in a metal grounded shield Installation in an isolated shield mm D mm mm mm mm mm mm mm 88 31 25 20 20 25 10 20 100 110 88 32 35 20 35 25 10 20 100 110 88 35 45 25 45 35 10 25 160 120 88 37 45 25...

Reviews: