3.4. Electrical connections
WARNING
: The operations must be undertaken in accordance with the safety warnings, ch.1.
In particular, the mains must be shut down before any of the work described below is begun.
Connections must be executed
in accordance with the wiring diagrams
provided inside the equipment,
which
remain the reference
.
Type of
cable
Connections
3G2.5²
Electrical power supply of
each equipment (230 V
single phase +
differential breaker 30 mA
min for each equipment).
WARNING
: High leakage
current.
=> Connection to the
ground imperative with a
1-mm² cable before
connecting the mains.
=> Do not connect
several equipments to the
same differential breaker.
2.5²
If the gates are powered
through long cables,
ensure the equipotential
bonding between the gates
forming a bank by
connecting them with a 1-
mm² ground wire.
0.75²
Connect the Emergency
command (Fire) if
desired.
Refer to the electrical diagrams.
0.75²
Connect the opening
commands and eventual
Inputs/Outputs.
Refer to the electrical diagrams.
Δ 30
m A
Δ 30
m A
230 VAC - 50 Hz