IFEX Technologies GmbH
IFEX 3000 Impulse Fire Fighting Technology
Nr.:IF3000-100
Instruction Manual
Instructions for Use and Operation
IFEX 3035 and IFEX 3050
P a g e | 9
Hansestr.18 D-27419 Sittensen
Mobile Fire Extinguishing Equipment
Date: 20.11.12
P a g e
|
9
3. Testing of the trolley
"
Caution
-
note warning
on page 7 ".
3.1
Check the trolley for damage and corrosion.
3.2
Check the tightness of the wheel caps on the axes.
3.3
Check the rotation of the wheels, if necessary grease the wheel caps.
3.4
Check the rubber of the wheels for damage.
3.5
Check the connection screws on the water container/trolley,(Hexagon screws KS 13).
3.6
Check the pressure bottle straps for damage and the velcro for strength
3.7
Check the connection strap of the gun for damage and its general condition.
4. Check of the water container and the mounted fittings
"
Caution
-
note warning
on page 7 ".
4.1
Disconnect thewater and air hoses from the container, and check the couplings.
4.2
Remove the air pressure bottle from the trolley.
4.3
Check the water container for external damage, scratches in the paint and corrosion.
4.4
Check the water connection and the fittings at the container and the couplings for
damage.
4.5
Check the air pressure connection and the fittings at the container and the couplings
for damages.
4.6
Check the manometer for damages.
4.7
Remove the filling unit from the container by turning the handle anti-clockwise.
4.7.1
Check the filling unit for damages.
4.7.2
Check the screw in thread and the o-sealing ring for damages.
4.7.3
Check the reducing valve and spindle thread for damages.
4.7.4
Check the fixedness of the handle fixing screw (KS13).
4.8
Empty the water container and check the inside visually.
4.9
Check the type plate and instruction sticker for damages and readability.
4.10
Demount the filter mesh (KS21), and check for damages.
4.11
After re-installation of all parts and re-connection of the water connection the safety
valve needs to be checked. Fill the container with water and air pressure. The valve
requires 6 bar +10% tolerance (6,6 bar). If the safety valve opens before reaching 6,0
bar, or if it fails to open at 6,6 bar, the valve is to be renewed.