Supply the AS-i DP gateway with a 24 V DC voltage (20...30 V PELV),
e.g. from the 24 V power supply DN2011 of ifm electronic. The
connection is made to the ter24 V and 0 V.
Operating and indicating elements
Information concerning the state of the masters and the connected
system is given via three diagnostic LEDs on the AS-i DP gateway.
• LED PWR/COM lights:
AS-i voltage present, at least one slave
was detected
• LED PWR/COM flashes: AS-i voltage present, but no slave was
detected correctly
• LED PROJ lights:
Projection mode active, the configuration
monitoring is deactivated
• LED PROJ flashes:
Projection mode active, changeover to
protected mode not possible as a slave
with the address 0 is connected
• LED CONF/PF lights:
Projected and current configuration do
not match
• LED CONF/PF flashes:
Periphery fault on at least one connected
slave
• LED Profibus DP lights:
Bus error Profibus DP
10