19
ifm
Device Manual AS-i IO-Link-Gateway (AC5225) Firmware V1.16
2017-11-20
IO-Link services
Standard services
>
5.2
Standard services
Standard ID object ............................................................................................................................... 19
Standard diagnosis object ................................................................................................................... 19
Standard device group object .............................................................................................................. 20
5153
>
5.2.1
Standard ID object
5154
This object range describes and identifies the AS-i slave. Identification with reference to
manufacturer ID and
device ID.
Request read standard ID object
Byte no.
Description
0
command code 16 = read standard
1
index 0 = ID object
2
length to be read = 5
Reply read standard ID object
Byte no.
Description
0
command code 80 = read standard OK
1
AS-i manufacturer ID (high) = 0x00
2
AS-i manufacturer ID (low) = 0x04
3
AS-i device ID (high) = 0x00
4
AS-i device ID (low) = 0x04
5
number of analogue AS-i inputs and outputs 0xDD (per 4 words transparent data)
>
5.2.2
Standard diagnosis object
5160
Query if module has an error on the AS-i side or functions without any error.
Request read standard diagnosis object
Byte no.
Description
0
command code 16 = read standard
1
index 1 = diagnosis object
2
length to be read = 1
Reply read standard diagnosis object
Byte no.
Description
0
command code 80 = read standard OK
1
standard diagnosis code:
0x00 = no error
0xFF = error, general
Summary of Contents for AC5225
Page 64: ......