IO-Link services
Device group services
>
5.3.6
Exchange acyclic process data
5244
IO-Link allows up to 32-byte process data in one IO-Link device. The connection of IO-Link devices
with process data > 4 words is not the focus of the AS-i IO-Link gateway. Nevertheless access to
these process data via the acyclic write / read requests described here is possible. Furthermore
access to the process data are also possible for a configuration software, irrespective of the AS-i
master used.
NOTE
► Data set acyclically also have to be reset acyclically!
Data set acyclically remain even if communication is interrupted.
Cyclic writing of data overwrites acyclically set values.
>
Write current output process data
6184
Request write output process data
Byte no.
Description
0
command code 21 = write device group
1
indices 31 / 32 = acyclic output process data ports 1 / 2
2
length = 2…29
3
IO-Link process data subindex: is required if more than 28 bytes or a data section have to be written
systematically, otherwise = 0
4...31
up to 28 bytes IO-Link process data
Reply write output process data
Byte no.
Description
0
command code 85 = write device group OK
>
Read current output process data
5249
Request read output process data image
Byte no.
Description
0
command code 20 = read device group
1
indices 31 / 32 = acyclic output process data ports 1 / 2
2
length = 1…32
Reply read output process data image
Byte no.
Description
0
command code 84 = read device group OK
1...32
up to 32 IO-Link process data bytes