32
ifm
Operating Instructions IO-Link Master with Profinet interface PowerLine 4 Ports IP 65 / IP 67 (AL1200)
2017-06-02
Configuration
>
8.2.1
Set-up
12759
On delivery, the AL1200 is configured with the
→
Factory settings
(
Before configuration with the LR DEVICE parameter setting software, the user must put the device into
operation. During set-up, the IP settings are configured via the Profinet interface (X21/X22).
In order to put the device into operation with LR DEVICE:
Prerequisites
>
The device is configured with the factory settings.
>
The device is properly connected with the LR DEVICE laptop/PC via the Profinet interface.
>
LR DEVICE is started
1 Scan network
►
Scan network for new IO-Link masters.
>
The following information is given under [ONLINE]:
- Article number (AL1200)
- MAC-ID of the device
2 Set network parameters
►
Under [ONLINE]: Click on [AL1200].
>
LR DEVICE shows all current network settings
►
Set the following parameters as required:
Parameters
Description
Possible values
[IP address]
IP address of the device
e.g. 172.18.65.50
[Subnet mask]
Subnet mask of the IP network
e.g. 255.255.255.0
[IP gateway address]
IP address of the network gateway
e.g. 172.18.65.0
[Profinet name]
Device name in the Profinet parameter setting software
► Observe the note!
When giving the Profinet name, the following restrictions apply:
Permitted characters:
– Lower case a-z
– Numbers 0-9
– Separators: Point, minus sign
Restrictions:
– The name may not end with a point or minus sign
– The name may not begin with a number
– The minus sign may not be directly before or after a point
►
Write the changed values to the device.
>
LR DEVICE stores the changed values on the device.
If successful:
>
In the [ONLINE] area: Under [Geräte], the Profinet name of the AL1200 appears.
>
LR DEVICE shows options for device configuration.
Summary of Contents for AL1200
Page 78: ......