64
ifm
Operating Instructions IO-Link Master with Profinet interface PowerLine 4 Ports IP 65 / IP 67 (AL1200)
2017-06-02
Appendix
>
12.1.1
Application
23710
Application
Application
I/O modules for field applications
Daisy-chain function
Voltage supply; communication interface
>
12.1.2
Electrical data
22819
Electrical data
Operating voltage
20...30 DC; (US; to SELV/PELV)
Current Consumption [mA]
300...3900; (US)
Protection class
III
Sensor supply US
Max. current load total [A]
3.6
>
12.1.3
Inputs / outputs
23711
Inputs / outputs
Total number of inputs and outputs
8; (configurable)
>
12.1.4
Inputs
22820
Inputs
Number of digital inputs
8; (IO-Link Port Class A: 4 x 2)
Switching level high [V]
11...30 DC
Switching level low [V]
0...5 DC
Digital inputs protected against short circuits
yes
>
12.1.5
Outputs
22821
Outputs (digital)
Output function
4; (IO-Link Port Class A: 4 x 1)
Max. current load per output [mA]
200
Short-circuit protection
yes
Summary of Contents for AL1200
Page 78: ......