66
ifm
Operating Instructions IO-Link Master with Profinet interface PowerLine 4 Ports IP 65 / IP 67 (AL1200)
2017-06-02
Appendix
>
12.1.9
Mechanical data
22825
Mechanical data
Weight [g]
272.2
Materials
Housing: PA; socket: brass nickel-plated
>
12.1.10
Electrical connection
7637
Voltage supply IN X31
Connector
M12
Wiring
1:
+ 24 V DC (US)
2:
GND (UA)
3:
GND (US)
4:
+24 V DC (UA)
Voltage supply OUT X32
Connector
M12
Wiring
1:
+ 24 V DC (US)
2:
GND (UA)
3:
GND (US)
4:
+24 V DC (UA)
Ethernet IN / OUT X21, X22
Connector
M12
Wiring
1:
TX +
2:
RX +
3:
TX -
4:
RX -
5:
-
Process connection IO-Link Ports Class A X01...X04
Connector
M12
Wiring
1:
+ 24 V DC (US)
2:
DI
3:
GND (US)
4:
C/Q IO-Link
5:
-
Summary of Contents for AL1200