Operating Instructions IO-Link Master with Profinet interface PowerLine 8 Ports IP 65 / IP 67 (AL1202)
2017-06-02
Electrical connection
>
6.2
IO-Link ports
22632
Ports X01...X04: For use as IO-Link port class A:
► Connect the connector of the IO-Link devices with the M12 sockets
X01 ... X04.
Tightening torque: 0.6...0.8 Nm
Maximum cable length per IO-Link interface: 20 m
► For the connection, use M12 connectors with protection rating IP 65
/ IP 67 or higher (z.B. EVC493).
Ports X05...X08: For use as IO-Link port class B:
► Connect the connector of the IO-Link devices via the adapter with
the M12 sockets X05 ... X08.
Tightening torque: 0.6...0.8 Nm
Maximum cable length per IO-Link interface: 20 m
► To connect the devices, use M12 connectors with protection rating
IP 65 / IP 67 or higher (z.B. EVC055).
► Cover the unused sockets with M12 protective caps (art. no.:
E73004).
Tightening torque 0.6...0.8 Nm
>
6.2.1
Input circuit
18629
The inputs of the M12 sockets 4 (pin 2) provide a type 2 behaviour according to standard EN61131-2,
the connected electronics must be rated for this electrically.
>
6.2.2
IO-Link circuits
1863
The IO-Link ports of the device meet the requirements of the IO-Link specification 1.0 bis 1.1.2.
The power supply of the connected IO-Link devices may only take place via the AL1202.
Further information:
→
Technical data
(