20
ifm
Operating Instructions IO-Link Master with Profinet interface PowerLine 8 Ports IP 65 / IP 67 (AL1202)
2017-06-02
Electrical connection
>
6.3
Connect the device
8577
► Disconnect power.
If voltage is supplied via a separate power supply:
► Connect device via the M12 socket X31 to 24 V DC (20 ... 30 V
SELV/PELV; accroding
to IEC 61010-1, secondary circuit with
maximum 30 V DC, supplied from mains circuit up to 300 V of
overvoltage category II)
.
Tightening torque: 0.6...0.8 Nm.
Maximum cable length: 25 m
► To connect the device, use M12 connectors with protection rating IP
65 / IP 67 or higher (e.g. E12430).
If voltage is supplied via additional AL12nn (daisy chain):
► Connect device via the M12 socket X31 to M12 socket of the
voltage output X32 of the requested AL12nn.
Tightening torque: 0.6...0.8 Nm
Maximum cable length: 25 m
► To connect the device, use T-coded M12 connectors with protection
rating IP 65 / IP 67 or higher (e. g. E12425)