Operation
>
9.6
Exchange IO-Link device
7775
To exchange an IO-Link device:
Requirement:
>
IO-Link device is with factory settings.
>
IO-Link device supports IO-Link standard 1.1 or higher.
1 Set data storage
►
Set the following parameters of the IO-Link port:
[Validation / Data Storage] = Type compatible V1.1 device with Restore
OR
[Port x IO-Link Validation / Data Storage] = Type compatible V1.1 device with Restore
►
Save changes.
2 Exchange IO-Link device
►
Disconnect old IO-Link device from AL1202.
►
Connect new IO-Link device with the same IO-Link port of the AL1202.
>
IO-Link master copies parameter values from the data memory to the new IO-Link device.