device manual AS-i DP-Gateway
B08
Exec. of PLC blocked by User
When the device was started the automatic start of the plc program was automatically interrupted by the user.
The left button of the button was activated during the switch-on operation.
6.1.6 FAT error (code F01 ...
F10)
(storage management):
(File Allocation Table)
F01
Bad FAT checksum
The checksum of the FAT contains an invalid value.
Possible cause:
Unacceptable interference on the 24V power supply cable during the storage operation of the
data in the flash device.
F02
Bad FAT header
The code in the header of the FAT contains an invalid entry.
Possible cause:
Unacceptable interference on the 24V power supply cable during the storage operation of the
data in the flash device.
F03
Bad FAT ID
The field code of a FAT area contains an invalid value.
Possible cause:
Unacceptable interference on the 24V power supply cable during the storage operation of the
data in the flash device.
F04
Virgin FAT found
The FAT does not contain an entry.
Possible cause:
Complete erasure of the flash device by the user.
F05
Bad NV field checksum
The checksum of the non-volatile data within the FAT contain an invalid value.
Possible cause:
Unacceptable interference on the 24V power supply cable during the storage operation of the
data in the flash device.
F06
Bad NV field ID
The field code of the non-volatile data contains an invalid value.
Possible cause:
Unacceptable interference on the 24V power supply cable during the storage operation of the
data in the flash device.
F07
NV pointer invalid range
The start address of the non-volatile data is outside the permitted area.
Possible cause:
Unacceptable interference on the 24V power supply cable during the storage operation of the
data in the flash device.
F08
FAT storage
An error has occurred during the storage of the FAT.
Possible cause:
Unacceptable interference on the 24V power supply cable during the storage operation of the
data in the flash device.
F09
NV field storage
An error has occurred during the storage of the non-volatile data.
Possible cause:
Unacceptable interference on the 24V power supply cable during the storage operation of the
data in the flash device.
Rectification:
Repeat command.
6-38