Function and features
• The controller
e
integrates one or two AS-i masters (AC1365/AC1366,
both in accordance with the AS-i version 3.0), a mini controller and a
Profibus DP interface (optional)
• It controls the exchange of data to the sensor/actuator level
• processes the peripheral data in the integrated processor (signal pre-
processing)
• works as stand-alone controller with exchange of data to the PC
(visualisation)
• communicates with the higher control level (in the gateway mode)
Programming interface RS232C
• Baud rate 4800 to 115,200 baud
• Max. distance between controller
e
and PC: 20 m
• Potential separation from the controller
e
power supply
• Programming cable E70320 for connection to PC required
Profibus-DP interface
• Baud rate 9600 to 12 MBaud
• Max. distance between controller
e
and DP master: depending on
the baud rate
• Potential separation from the controller
e
power supply
• Up to 31 controllers connected in parallel per segment
• Pin connection: pin 3: signal B, pin 8: signal A
Installation
Fix the controller
e
onto a 35 mm rail which has an electrically safe gro-
und connection. The protection rating of the unit is IP20, therefore it
should be mounted in a protected location (e.g. control cabinet).
Ensure a condensation-free environment. Avoid excessive dust,
vibration and shock. The air circulation through the vents must
not be impeded.
Avoid installation in direct vicinity of frequency inverters.
9