6
• connector with screw terminals, order no� E40173
The outputs are short-circuit proof up to 100 mA� The outputs can be configured
as either normally closed or normally open�
In addition an analogue signal can be provided on output [OU 1] (0/4���20 mA)
(e�g� acceleration values)�
5.1 Limited voltage / current
According to UL508 the device shall be supplied from an isolating source having a
secondary UL-listed fuse rated
a) max 5 A for voltages 0���20 Vrms (0���28�3 Vp) or
b) 100/Vp for voltages of 20���30 Vrms (28�3���42�4 Vp)�
5.2 Wiring
4
3
Supply L+ (24 V DC ± 20%)
Supply L- (GND)
2
1
8
7
6
5
12
11
9
24
23
20
19
16
15
1
4
2
3
BN
BK
WH
BU
4
1
3
2
BK
BN
BU
WH
OU1: switch/analog
OU2: switch
IN 1: (4...20 mA / pulse)
IN 1 (GND1)
IN 2: (4...20 mA / pulse)
IN 2 (GND2)
22
21
18
17
14
13
10
1
4
2
3
BN
BK
WH
BU
1
4
2
3
BN
BK
WH
BU
Terminal
Connection
Description
1
L+
24 V DC supply
2
L-
GND
3
OU 1
Early warning output
4
OU 2
Main alarm output
5
IN 1
Process value input 1
6
GND1