background image

8

•  the output [OU 2] clocks at 1 Hz
•  the [SENS] LED flashes green

5.4  Ethernet connection

The RJ45 socket is used for the connection to the Ethernet�

Ethernet cables can be supplied as accessories, e.g.:

  cross-over cable, 2 m, article no� EC2080
  cross-over cable, 5 m, article no� E30112

6  Operation

The input signals are continuously detected and permanently monitored according 

to the set tasks (parameters)� The monitoring tasks of the process values and ob-

jects (e�g� vibration monitoring and diagnostics) are defined on the PC by means 

of software (article number VES004) and then transferred to the diagnostic elec-

tronics as parameter set via Ethernet interface� The characteristic values (objects) 

in the frequency range are monitored in sequence (multiplex mode) while the time 

range is monitored simultaneously� 
Alarm states of the set objects can be displayed on up to 2 digital outputs� Output 

1 (OU 1) can also be used as analogue output (e�g� for transferring the total 

vibrations to ISO 10816)� Alarm states of objects that are assigned to one of 

the 4 dynamic inputs (sensor 1���4) are displayed by the respective LEDs of the 

diagnostic electronics�
The operating state of the electronics and the sensors is also displayed via the 

multi-colour LEDs on the device�

6.1  Settings 

The diagnostic electronics and the visualisation of online data (time signal, 

frequency spectra, object value, history data, ���) are configured via the software 

for the diagnostic electronics (article number VES004)� An exact description of the 

functions and parameters can be found in the user manual or in the online help of 

the software�

Summary of Contents for efector 800 VSE002

Page 1: ...Operating instructions Diagnostic electronics for vibration sensors VSE002 VXE002 VXE003 VYE001 VYE002 VYE003 VYE104 80226772 01 07 2019 UK ...

Page 2: ...5 5 Electrical connection 5 5 1 Limited voltage current 6 5 2 Wiring 6 5 2 1 Wiring of the sensors 1 4 S1 S4 according to the sensor 7 5 3 Connection of the sensors 7 5 3 1 Monitoring the sensor cable 7 5 4 Ethernet connection 8 6 Operation 8 6 1 Settings 8 7 Indicators LEDs 9 8 Maintenance repair and disposal 10 9 Scale drawing 10 ...

Page 3: ...s Protection against accidental contact safety from finger contact to IP 20 for qualified personnel is only ensured if the terminals have been completely inserted Therefore the unit must always be mounted in a control cabinet of at least IP 54 which can only be opened using a tool For DC units the external 24 V DC supply must be generated and supplied according to the requirements for safe extra l...

Page 4: ...alogue signals for current value above and or below the limit value of up to 24 indicators objects of the dynamic signals e g vibration in the time range or frequency range FFT and or H FFT Monitoring of the objects is possible with regard to up to 2 process categories e g load and rotational speed Internal trend memory with RTC time stamp with flexible storage intervals for each object Counter fu...

Page 5: ... 1 Installation of the sensors Adhere to the SELV criteria when the sensors are connected so that no dan gerous contact voltages are applied to the sensor or transferred to the device Sensor and diagnostic electronics supply are not electrically isolated 5 Electrical connection The unit must be connected by a qualified electrician The national and international regulations for the installation of ...

Page 6: ...source having a secondary UL listed fuse rated a max 5 A for voltages 0 20 Vrms 0 28 3 Vp or b 100 Vp for voltages of 20 30 Vrms 28 3 42 4 Vp 5 2 Wiring 4 3 Supply L 24 V DC 20 Supply L GND 2 1 8 7 6 5 12 11 9 24 23 20 19 16 15 1 4 2 3 BN BK WH BU 4 1 3 2 BK BN BU WH OU1 switch analog OU2 switch IN 1 4 20 mA pulse IN 1 GND1 IN 2 4 20 mA pulse IN 2 GND2 22 21 18 17 14 13 10 1 4 2 3 BN BK WH BU 1 4 ...

Page 7: ...round GND of the sensor supply The SELV criteria must therefore be met for the DC supply safety extra low voltage circuit electrically isolated from other circuits not grounded If the DC circuit is to be grounded e g due to national regulations the PELV criteria must be adhered to safety extra low voltage circuit electrically isolated from other circuits 5 3 Connection of the sensors Adhere to the...

Page 8: ...requency range are monitored in sequence multiplex mode while the time range is monitored simultaneously Alarm states of the set objects can be displayed on up to 2 digital outputs Output 1 OU 1 can also be used as analogue output e g for transferring the total vibrations to ISO 10816 Alarm states of objects that are assigned to one of the 4 dynamic inputs sensor 1 4 are displayed by the respectiv...

Page 9: ... Flashes green yellow alternately Teach process active LED 2 ditto for sensor 2 LED 3 ditto for sensor 3 LED 4 ditto for sensor 4 LED 5 for system Lights green System OK monitoring running Lights yellow System OK no monitoring due to parameter setting self test or FFT mode Flashes green yellow alternately Monitoring not possible faulty parameter set Flashes green red alternately System error EEPRO...

Page 10: ...easures are necessary Only the manufacturer is allowed to repair the unit After use dispose of the unit in an environmentally friendly way in accordance with the applicable national regulations 9 Scale drawing 1 Ethernet interface Technical data and further information at www ifm com ...

Reviews: