5.1  Definition of requested value

 

► Loosen the lock nut.

 

► Turn the knurl until the requested value just becomes visible on the setting 

scale. → Example in figure 2: requested value = 10 l/min.

 

► Tighten the lock nut.

5.2  Adjustment to existing flow

 

► Let the normal flow circulate in the installation.

 

► Loosen the lock nut.

 

► Set the switch point with the knurl.

 -If the LED lights before setting: turn the knurl in the direction [+] until the LED 

goes out. Then turn in the opposite direction [-] until the LED lights.

 -If the LED does not light before setting: turn the knurl in the direction [-] until 

the LED lights.

 

► Tighten the lock nut.
Correlation between number of the turns of the knurl (SET) and switch point in l/

min (typical course of the measurement curves):

SET

SBU325

SBU324

SBU323

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

0

10

20

30

40

50

Q  [l/min]

60

70

80

90

100

The diagram shows the typical course of the measurement curves for coolants at 20 °C.

Summary of Contents for efector300 SBU3

Page 1: ...Operating instructions Mechatronic flow sensor SBU3 706020 00 03 2011 UK...

Page 2: ...he product materials see technical data with the media to be monitored in all applications The device shall be supplied from an isolating transformer having a secondary Listed fuse rated either a max...

Page 3: ...is adjustable 3 Installation Ensure that the system is free of pressure during installation Ensure that no media can leak at the mounting location during installa tion The unit provides 5 connections...

Page 4: ...Connect the unit as follows 3 1 4 2 L L 1 3 4 For information about available sockets connectors see www ifm com Products Accessories 5 Switch point setting There are 2 possibilities Definition of re...

Page 5: ...ights before setting turn the knurl in the direction until the LED goes out Then turn in the opposite direction until the LED lights If the LED does not light before setting turn the knurl in the dire...

Page 6: ...t C switching output 7 Maintenance repair and disposal In case of correct use no maintenance and repair measures are necessary In case of strongly polluted media mount a filter in front of the inlet I...

Page 7: ...7 UK 8 Scale drawing 30 G 2 1 G 2 1 80 62 24 150 167 40 G 2 1 80 68 6 40 6 3 26...

Page 8: ...bility of value of measuring range 1 Accuracy of value of measuring range 5 Response time s 0 01 Materials wetted parts stainless steel 316 1 4401 aluminium anodised PEEK O ring FPM Viton Housing mate...

Reviews: