16
9.2.2 Settings for limit value monitoring with OUT2
► Select [OU2] and set the switching function:
[Hno] = hysteresis function/normally open,
[Hnc] = hysteresis function/normally closed,
[Fno] = window function/normally open,
[Fnc] = window function/normally closed�
► Select [SP2] and set the value at which the output switches�
► Select [rP2] and set the value at which the output switches back�
9.2.3 Scaling of the analogue value for volumetric flow
► Select [OU2] and set the function:
[I] = current signal proportional to volumetric flow (4…20 mA);
► Select [ASP] and set the value at which the minimum output value is
provided�
► Select [AEP] and set the value at which the maximum output value is
provided�
9.3 Settings for monitoring of consumed quantities
9.3.1 Settings for quantity monitoring by pulse output
► [Select [OU1] and set [ImP]�
► Select [ImPS] and set the volumetric flow quantity at which 1 pulse is
provided (→ 9.6).
► Select [ImPR] and set [YES]
> Pulse repetition is active� Output 1 provides a counting pulse when the
value set in [ImPS] is reached�
9.3.2 Settings for quantity monitoring using the preset meter
► Select [OU1] and set [ImP]�
► Select [ImPS] and set the volumetric flow quantity at which output 1
switches (→ 9.6).
► Select [ImPR] and set [no]
> Pulse repetition is not active� The output switches ON if the value set in
[ImPS] is reached� It remains switched until the meter is reset�
9.3.3 Settings for meter reset controlled by the program
► Select [rTo] and continue with a) or b)�
a) Reset the meter manually
► Press [Set] until [rES�T] is displayed, then press [Mode/Enter] briefly�
b) Enter the value for time-controlled reset
► Press [Set] until the requested value is displayed (intervals from 1 hour
to 8 weeks), then press [Mode/Enter] briefly�