22
ifm
Programming Manual AS-i Gateway AC14 (4.2.x)
12/2017
System configuration
Configure Ethernet interface
>
6.2
Configure Ethernet interface
Available fieldbus stacks ........................................................................................................................22
Add fieldbus stack ..................................................................................................................................23
17701
► Familiarise yourself with the following CODESYS functions!
Menu command "Attach device"
→ Online help > CODESYS Development System > Devices > Attach Device...
Configure EtherCAT (master)
→ Online help > Fieldbus support > EtherCAT Configuration Editor
Configure modbus TCP (master/slave)
→ Online help > Fieldbus support > Modbus Configuration Editor
>
6.2.1
Available fieldbus stacks
18518
The Ethernet internet (X3) of the device can be declared and operated as an additional fieldbus
interface. For this, a fieldbus stack must be assigned to the interface in CODESYS. Presently, the
device supports the following fieldbus stacks:
Designation
Fieldbus
Manufacturer
Modbus TCP Master
Modbus TCP
3S - Smart Software Solutions GmbH
Modbus TCP Slave
Modbus TCP
3S - Smart Software Solutions GmbH