IO-Link Master with PROFINET Interface DataLine 8 Ports IP 65 / IP 66 / IP 67
65
>
9.3.4
Configure IO-Link ports
52481
You can access the configuration of the IO-Link ports via the slots 1.2 ... 1.9 of the AL1302. The
following assignment applies
Slot
IO-Link port of the AL1302
1.2
Port X01
1.3
Port X02
...
...
1.9
Port X08
The available PROFINET modules are defined in the GSD file (
→
PROFINET modules
(
)). A
PROFINET module determines the following properties of an IO-Link port:
Operating mode (IO-Link, DI, DO, deactivated)
Type and length of the process data
Optional data (fail-safe values, device validation, data storage, cycle time, events)
The following table shows the available parameters depending on the selected operating mode:
Operating mode of the IO-Link
ports
Available parameters
Fail-safe
mode
Pattern
Value
Validation /
Data
storage
Vendor
ID (VID)
Device ID
Port cycle
time
IO-Link
events
DI: digital input
--
--
--
--
--
--
X
DO: digital output
X
--
--
--
--
--
X
IO-Link: input
--
--
X
X
X
X
X
IO-Link: output
X
X
X
X
X
X
X
IO-Link: input and output
X
X
X
X
X
X
X
-- = not available
X = available
To configure an IO-Link port of the AL1302:
►
Drag the required PROFINET module from the hardware catalogue and drop it on the slot of the IO-Link port.
►
Double click on the slot of the IO-Link port
►
Set the parameters as required (→
Parameters of the IO-Link ports
(→ S.
►
Configure unused IO-Link ports with PROFINET module "Deactivated".
►
Repeat the steps to configure further IO-Link ports.
►
Save the project.