IO-Link Master with PROFINET Interface DataLine 8 Ports IP 65 / IP 66 / IP 67
81
>
Parameters of the IO-Link ports
34528
Parameter
Description
Possible values
[Fail-safe mode]
Behaviour in case the PROFINET
connection is interrupted
No Fail Safe
deactivated
Fail Safe Reset Value reset to default values
Fail Safe Old Value
maintain the most recent valid process
value
Fail Safe with Pattern set user-defined values
[Pattern Value]*
required values for the process
data in case the connection is
interrupted
(as hexadecimal value)
Pattern depends on the size of the
selected PROFINET module
Per byte:
0x00 ... 0xFF
[Port cycle time]
Cycle time of the data transmission at
the IO-Link port
as fast as possible
The device automatically sets the
fastest possible cycle time
2.0 ms
...
128.0 ms
2 milliseconds
...
128 milliseconds
[Validation / Data
Storage]
Supported IO-Link standard and
behaviour of the AL1302 when a new
IO-Link device is connected to the
IO-Link port
no check and clear
no verification of the vendor ID and
device ID
no data storage
Type compatible V1.0
device
IO-Link device is compatible with
the V1.0 IO-Link standard
Verification whether it is an IO-Link
device of the same type (validation
via vendor ID and device ID)
no data storage
Type compatible V1.1
device
IO-Link device is compatible with
the V1.1 IO-Link standard
Verification whether it is an IO-Link
device of the same type (validation
via vendor ID and device ID)
no data storage
Type compatible V1.1
device with
Restore
IO-Link device is compatible with
the V1.1 IO-Link standard
Verification whether it is an IO-Link
device of the same type (validation
via vendor ID and device ID)
The IO-Link master saves the
parameter values of the connected
IO-Link device; modifications of
the parameter values are also
stored (
→ observe the note!)
When connecting an IO-Link device
with factory settings, the parameter
values stored in the IO-Link master
are restored automatically on the
IO-Link device.