Device Manual IO-Link Master with Modbus interface CabinetLine 8 Ports IP 20 (AL1940)
05 / 2018
Configuration
Modbus
>
8.3.8
Read device information
11039
The user can read device information using the FC43.
The AL1940 supports the following data records ("Read Device ID code"):
Basic Device Identification (0x01): contained data objects:
→ Modbus specification
Regular Device Identification (0x02): contained data objects:
→ Modbus specification
Specific Device Identification (0x04): contained data objects:
Object ID
Object name / description
Data type
Possible values
0x00
VendorName
ASCII string
ifm electronic
0x01
ProductCode
ASCII string
1940
0x02
MajorMinorRevision
ASCII string
e.g. V1.001
0x03
VendorURL
ASCII string
www.ifm.com
0x04
ProductName
ASCII string
IO-Link Master CL MOD 8P IP20
0x05
ModelName
ASCII string
1940
0x06
UserApplicationName
ASCII string
MODBUS IO-Link master
>
8.3.9
Control IO-Link master
23382
The user can control the IO-Link master using the following acyclic commands:
"Reboot":
→
Command 0x40 – Reboot
(
"Factory Reset":
→
Command 0x50 – Factory Reset
(
The commands use the process mechanisms of the acyclic command channel (
→
Use acyclic services
(
>
8.3.10
Configure IO-Link devices
9031
The IO-Link master supports the configuration of the connected IO-Link devices from the Modbus
projection software. The parameters of an IO-Link device are set via IO-Link index and subindex. The
number of the configurable parameters depends on the connected IO-Link device.
Available parameters of the IO-Link devices:
→ IO Device Description (IODD) of the IO-Link
device
The user can read and write IO-Link index and subindex using the following methods:
>
Acy clic com m unication: →
Use acyclic services