16
ifm
Programming Manual BasicController relay CR0431 v03.03.00
05 / 2018
System description
Hardware description
>
Input group IN0...IN3
14568
These inputs are a group of multifunction channels.
These inputs can be used as follows (each input separately configurable):
• analogue input 0...20 mA
• analogue input 0...10 V
• analogue input 0...32 V
• voltage measurement ratiometric 0...1000 ‰
• binary input plus switching (BL) for positive sensor signal (with/without diagnosis)
• binary input minus switching (BH) for negative sensor signal
• fast input for e.g. incremental encoders and frequency or interval measurement
→ chapter
Possible operating modes inputs/outputs
(
Sensors with diagnostic capabilities to NAMUR can be evaluated.
All inputs show the same behaviour concerning function and diagnosis.
Detailed description
→ chapter
Address assignment inputs / outputs
(
Configuration of each input is made via the application program:
• FB
INPUT
(
) > input MODE
• FBs
FASTCOUNT
(
),
INC_ENCODER
(
) or
PERIOD
(
>
If the analogue inputs are configured for current measurement, the device switches to the safe
voltage measurement range (0...32 V DC) and the output RESULT is set accordingly in the
function block INPUT when the final value (23 mA for > 40 ms) is exceeded. After about one
second the input automatically switches back to the current measuring range.
>
Input group IN4...IN7
14569
These inputs are a group of multifunction channels.
These inputs can be used as follows (each input separately configurable):
• binary input plus switching (BL) for positive sensor signal
• input for resistance measurement (e.g. temperature sensors or fuel sensors)
→ chapter
Possible operating modes inputs/outputs
(
Sensors with diagnostic capabilities to NAMUR can be evaluated.
► Configuration of each input is made via the application program:
• FB
INPUT
(
) > input MODE