177
ifm
Programming Manual BasicController relay CR0431 v03.03.00
05 / 2018
ifm function elements
ifm function elements for the device CR0431
>
Parameters of the outputs
8081
Parameter
Data type
Description
OUTPUT
BOOL
TRUE:
output is activated
FALSE:
output is deactivated
CURRENT
WORD
only available for current controlable outputs:
current output current in [mA]
RESULT
BYTE
feedback of the function block
(possible messages → following table)
Possible results for RESULT:
Value
dec | hex
Description
0
00
FB is inactive
1
01
FB execution completed without error
– data is valid
2
02
function block is active (action not yet completed)
3
03
function block is active
– valid values not yet available
128
80
undervoltage on VBBx
129
81
overvoltage on VBBx
130
82
channel setting is invalid
132
84
mode setting is invalid
136
88
filter setting is invalid
141
8D
a wire break was detected
(for binary output, plus switching (BH) with diagnosis)
142
8E
a short circuit was detected
(for binary output plus switching (BH) with diagnosis)
145
91
current at the output is too high
(for binary output plus switching (BH) with diagnosis and protection)