Reset Ethernet parameters
w
Reset the Ethernet parameters to factory setting:
u
Remove all cable connections from the device.
u
Insert an electrically conductive bridge between pin 2 and pin 4 on the connection “voltage
supply PWR”.
u
Connect the device to the voltage supply.
w
The LEDs of the signal bar (yellow) are on one after the other. Then LED 4 of the signal
bar (yellow) flashes at 8 Hz.
u
As soon as the LEDs of the signal bar (yellow) flash at 8 Hz, disconnect the unit.
u
Remove the bridge.
u
Connect the device to the voltage supply.
w
The Ethernet parameters are reset.
7.2 Connecting the functional earth
For trouble-free operation:
u
Connect the device to an earth potential free from external voltage.
Connect the mounting plate to functional earth.
Fig. 2: Mounting plate with mounted device
When the device is mounted on a mounting plate:
u
Connect one of the 4 mounting bolts on the back of the device to the mounting plate.
u
Connect the mounting plate to an earth potential free from external voltage.