DTE601 DTE602 DTE604 DTE605
RFID compact unit
14
7 Electrical connection
The device must be connected by a qualified electrician.
Device of protection class III (PC III).
The electrical supply must only be made via PELV/SELV circuits.
u
Disconnect power before connecting the device.
ATTENTION
The IP rating indicated in the data sheet is only guaranteed if the M12 connectors are firmly
screwed. The device can be damaged by insufficiently tightened M12 connectors.
u
Screw the M12 connector to the device applying 1 to 1.5 Nm.
7.1 Wiring
PWR voltage supply
u
Connect the device to a voltage supply using an M12 connection cable.
Pin assignment
Wiring
4
2
1
3
5
1
24 V DC
2
Digital input / output 2
3
0 V
4
Digital input / output 1
5
not connected
Ethernet
u
Connect the device to a PC using a suitable M12 Ethernet connection cable.
Pin assignment
Wiring
1
2
3
4
1
TD+
2
RD+
3
TD-
4
RD-
For trouble-free operation:
u
use a shielded M12 Ethernet connection cable.
The following parameters are preset at the factory:
Parameter
Preset
IP address
192.168.0.79
Gateway address
192.168.0.100
Subnet mask
255.255.255.0
Auto-negotiation
On
DHCP
Off
The settings can be changed via the unit's web server or via a connected PC.