ifm
Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Set-up
Parameter setting of the Profibus host
156
9.8.3
Define Profibus DP modules
Module 1 – Binary inputs/outputs of single/A slaves of AS-i master 1...................................... 157
Module 2 – Binary inputs/outputs of single/A slaves of AS-i master 2...................................... 158
Module 3 – Binary inputs/outputs of B slaves of AS-i master 1 ................................................ 159
Module 4 – Binary inputs/outputs of B slaves of AS-i master 2 ................................................ 160
Module 5 – Multiplexed analogue inputs of AS-i masters 1/2................................................... 161
Module 6 – Multiplexed analogue outputs of AS-i masters 1/2................................................. 162
Module 7 – Command channel ................................................................................................. 163
Module 8 – Data transmission between Profibus DP master and PLC in the ControllerE ....... 166
Module 9 – Data transmission between PLC in the ControllerE and the Profibus DP master . 166
Module 10 – Parallel analogue inputs....................................................................................... 167
Module 11 – Parallel analogue outputs..................................................................................... 167
Module 12 – Extended command channel................................................................................ 168
5559
The text of the different options of the modules always starts with the module number (
photo in
section Programming software (
→
page
)). So all options in the module list of the hardware
catalogue starting with "1:" are options of the first module in the device definition.
The first module for example defines the number of binary I/O data bytes of single or A slaves of AS-i
master 1 which are to be transferred to the Profibus master via Profibus DP.
NOTE
The maximum data length of all 12 modules must not exceed 152 input bytes and 152 output bytes.
Example:
Siemens S7 with AS-i gateway AC1376
For the advanced Profibus DP user it is also possible to use length codes other than those indicated
as long as the maximum lengths of the modules are not exceeded.