Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Set-up
Parameter setting of the Profibus host
164
Overview of the commands in the DP module 7
5589
command no.
Contents of ...
dec
hex
Description
Byte 2
Byte 3
Byte 4
►
read master flags
MM000000
0 —
01 01
response:
MM000000
Master flags in module 7
(
→
)
►
change operating mode
MM000000
AS-i master
preset operating
mode
—
02 02
response:
MM000000
AS-i master
current operating
mode
—
►
read current slave configuration
MMXSSSSS
— —
03 03
response:
MMXSSSSS
slave configuration data
►
read projected slave configuration
MMXSSSSS
— —
04 04
response:
MMXSSSSS
slave configuration data
►
change projected slave configuration
MMXSSSSS
slave configuration data
05 05
response:
MMXSSSSS
slave configuration data
►
read slave parameters
MMXSSSSS
— —
06 06
response:
MMXSSSSS
projected
parameters
current
parameters
►
change projected slave parameters
(default parameters)
MMXSSSSS
projected
parameters
—
07 07
response:
MMXSSSSS
projected
parameters
—
►
read
LAS
MMXSSSSS
— —
08 08
response:
MMXSSSSS
slave addresses from address group
►
read
LDS
MMXSSSSS
— —
09 09
response:
MMXSSSSS
slave addresses from address group
►
read
LPF
MMXSSSSS
— —
10 0A
response:
MMXSSSSS
slave addresses from address group
►
read
LPS
MMXSSSSS
— —
11 0B
response:
MMXSSSSS
slave addresses from address group
12 0C
reserved
—
—
►
read telegram error counter
MMXSSSSS
— —
13 0D
response:
MMXSSSSS
error counter
►
read configuration error counter
MM000000
— —
14 0E
►
response:
MM000000
error counter
►
read AS-i cycle counter
MM000000
— —
15 0F
►
response:
MM000000
current count value of the cycle
counter
►
change current slave parameters
MMXSSSSS
parameters —
16 10
response:
MMXSSSSS
reflected
parameters
—
17
18
11
12
reserved —
—
—