ifm
Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Set-up
Parameter setting of the Profibus host
167
Module 10 – Parallel analogue inputs
5593
Module 10
Parallel analogue inputs of up to 30 AS-i slaves, 1/2/4 words per AS-i slave; the
slave number and the number of analogue channels are defined by Profibus DP
parameters.
data length = 4 words
(default) All 4 channels of a total of up to 15 slaves on masters 1 and 2 are
transmitted.
Selection of the slaves to be transmitted via Profibus DP device
parameters (
chapter Device-specific Profibus DP parameters
(
→
)).
data length = 2 words
From slave 1 onwards (of up to 30 slaves) on master 1, the channels 1
and 2 are transmitted.
Contents
data length = 1 word
From slave 1 onwards (of up to 30 slaves) on masters 1 and 2, channel 1
each is transmitted.
Length
0...60 words inputs (if not used: length = 0)
Module 11 – Parallel analogue outputs
5594
Module 11
Parallel analogue outputs of up to 30 AS-i slaves, 1/2/4 words per AS-i slave; the
slave number and the number of analogue channels are defined by Profibus DP
parameters.
data length = 4 words
(default) All 4 channels of a total of up to 15 slaves on masters 1 and 2 are
transmitted.
Selection of the slaves to be transmitted via Profibus DP device
parameters (
chapter Device-specific Profibus DP parameters
(
→
)).
data length = 2 words
On slave 1 (up to 30 slaves) on master 1, the channels 1 and 2 are
transmitted.
Contents
data length = 1 word
On slave 1 (up to 30 slaves) on masters 1 and 2, channel 1 is transmitted.
Length
0...60 words outputs (if not used: length = 0)
NOTE
If analogue outputs are also triggered in module 6, the value written in module 6 is overwritten with the