ifm
Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
DP module 12: extended command channel
Commands in the extended command channel
252
Response from device to host in the normal case
: Safety-at-Work monitor has triggered
Word no.
Value [hex.]
Meaning
1
071F
copy of the request
command processed, no error occurred
2 0000
reserved
3
001E
reflected command data
4
2211
2x = output circuit 1 red;
x2 = invalid,
word 5;
11 = protective operation, output circuit 1 off
5
0003
00 = OSSD2 green
03 = OSSD1 not green, provides 3 modules which are not green
6
0421
04 = red permanently lit
21 = module 33
7
0422
04 = red permanently lit
22 = module 34
8
0423
04 = red permanently lit
23 = module 35
9…11 xxxx
not relevant, because low byte of 5th word = 03
3 modules relevant
12…17 xxxx
not relevant, because high byte of 5th word = 00
green, no module relevant
18
0100
01 = field nubmer 1
Response from device to host in case of a fault
Word no.
Value [hex.]
Meaning
1
871F
copy of the request
E=1: error when executing the command
2 0000
reserved
3
0011
error code=11: no slave with the profile S-7.F.F on the slave address
4…18 xxxx
not
changed