ifm
Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Function
Introduction AS-i data
31
strSafetyList – fields with safety slave contacts
5345
Bit / safety slave address, contact
Word
no.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
7C2
7C1
6C2
6C1
5C2
5C1
4C2
4C1
3C2
3C1
2C2
2C1
1C2
1C1
res
res
1
15C2 15C1 14C2 14C1 13C2
13C1 12C2
12C1 11C2
11C1 10C2
10C1 9C2
9C1 8C2
8C1
2
23C2 23C1 22C2 22C1 21C2
21C1 20C2
20C1 19C2
19C1 18C2
18C1 17C2
17C1 16C2
16C1
3
31C2 31C1 30C2 30C1 29C2
29C1 28C2
28C1 27C2
27C1 26C2
26C1 25C2
25C1 24C2
24C1
Examples:
1C1_= safety slave 1, contact 1 open
1C2_= safety slave 1, contact 2 open
31C1_= safety slave 31, contact 1 open
31C2_= safety slave 31, contact 2 open