DP module 12: extended command channel
Commands in the extended command channel
313
Example:
read device features
Request from fieldbus master to device
Word no.
Value [hex.]
Meaning
1
0669
M=0: AS-i master 1
UID=06: user ID changes e.g. to 6
69 = command number 105
2 0000
reserved
3...18 xxxx
not
used
Response from device to fieldbus master
Word no.
Value [hex.]
Meaning
1
0669
E=0: command processed, no error occurred
reflected command data
2 0000
reserved
3 0008
0008
hex
= 0000 0000 0000 1000
bin
2M=0: device has 1 AS-i master
DP=0: fieldbus interface Profibus DP not available
EN=0: Ethernet programming interface not available
PLC mode = 08
gateway mode
4 000B
Anybus type = 000B
ifm Profibus DP
5
0002
flash memory type
6 1000
hardware
version
7 0002
1st part of the RTS firmware version (here: 02.218B)
version number 02.xxxx
8 218B
2nd part of the RTS firmware version (here: 02.218B)
release number xx.218B
9 0000
1st part of the AS-i master 1 firmware version (here: 0.238A)
version number 0.xxxx
10 238A
2nd part of the AS-i master 1 firmware version (here: 0.238A)
version number x.238A
11 0000
1st part of the AS-i master 2 firmware version (here: 0.238A)
version number 0.xxxx
12 238A
2nd part of the AS-i master 2 firmware version (here: 0.238A)
version number x.238A
13
0196
Linux kernel version: 406
14
0A6E
Linux ramdisk version: 10.110
15...18 xxxx
not