ifm
Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Acyclic services for Profibus DPV1
Acyclic command in the DPV1 command channel
331
12.8.5
Acyclic command 05 – set the operating mode of the AS-i
master
5867
Request from fieldbus master to device
Bit
Offset
Word no.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
UID
command request = 65
hex
2
reserved = 0
command number = 05
dec
= 05
hex
3
reserved = 0
MOD
4...19
not used
not used
Legend:
UID
user ID
1 byte
00…FF
hex
= 0…255
dec
MOD
opperating mode
1 byte
00 = set master to the normal mode (protected mode)
01 = set master to the projection mode
Response from device to fieldbus master in the normal case
Bit
Offset
Word no.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
reflected user ID
Command status (
→
page
) = 6F
hex
2
reserved = 0
reflected command number
3...19
not changed*)
not changed*)
*)
IMPORTANT:
For the query read only the required bytes!
Unused bytes can contain information of previous queries.
Response from device to fieldbus master in case of a fault
Bit
Offset
Word no.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
reflected user ID
Command status (
→
page
) = 6B
hex
2
reserved = 0
reflected command number
3
reserved = 0
error code
4...19
not changed*)
not changed*)
Possible error codes:
Value [hex.]
Meaning
03
slave with address 0 connected