Acyclic services for Profibus DPV1
Acyclic command in the DPV1 command channel
354
Description of the different fields in word no. 4 for [data call 1/2]
data call 1
data call 0
Value
[hex.]
Value
[bin.]
Value
[hex.]
Value
[bin.]
Meaning
8
1000
0
0000 protective operation, everything ok (also not available, not configured or depending output
circuits are displayed as "ok")
9
1001
1
0001 protective operation, output circuit 1 off
A
1010
2
0010 protective operation, output circuit 2 off
B
1011
3
0011 protective operation, both output circuits off
C
1100
4
0100 configuration operation: power on
D 1101 5 0101
configuration
operation
E
1110
6
0110 reserved / not defined
F
1111
7
0111 configuration operation: fatal device error, RESET or device exchange required
-
-
> 8
1xxx no current diagnosis information available, please wait
Description of the different fields in word no. 5 for [OSSD1/2 not green]
Value [hex.]
Value [bin.]
Meaning
0
0000
no module, responses of the data calls in the words 6...17 are not relevant
1
0001
the number of POUs in the output circuit is 1
… …
…
6
0110
the number of POUs in the output circuit is 6
7
0111
the number of POUs in the output circuit is > 6
> 8
1xxx
reserved / not defined
Description of the different fields in word no. 6...17 for [colour output circuit]
Module address 1...6 in output circuit 1/2: Indicates the index of the module of the configuration. The module address which was
defined in the program ASIMON is indicated.
Value [hex.]
Value [bin.]
Meaning
0 0000
green,
continuous
1 0001
green,
flashing
2 0010
yellow,
continuous
3 0011
yellow,
flashing
4 0100
red,
continuous
5 0101
red,
flashing
6 0110
grey,
off