ifm
Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Acyclic services for Profibus DPV1
Acyclic command in the DPV1 command channel
395
Example:
reset all slave error counters
Request from fieldbus master to device
Word no.
Value [hex.]
Meaning
1
0965
09 = user ID changes e.g. to 9
65 = command request
2
0061
60 = command number 96
3 0012
command number = 12
reset all slave error counters
4...19 xxxx
not
used
Response from device to fieldbus master
Word no.
Value [hex.]
Meaning
1
096F
09 = reflected user ID
6F = command status is "done" (no error)
2
0061
61 = reflected command number
3...19 xxxx
not
changed