ifm
Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Operation
Set AS-i address of the safety monitor
450
Diagnostics of
AS-i master 1
Safety Master 1
OK
130
ESC
Step 4:
AC1375: Menu screen not available.
►
Press [ ] to scroll to requested safety master.
.
Slave List of
AS-i master 1
Safety Master 1
OK
130
ESC
Step 5:
AC1375: Menu screen not available.
►
Select safety master with [OK].
.
Safety Monitor
Read Monitor
Trigg.Slave
OK
141
ESC
Step 6:
►
Press [ ] to scroll to [Enable Monitor].
Safety Monitor
Trigg.Slave
Enable Monitor
OK
141
ESC
Step 7:
►
Select [Enable Monitor] with [OK].
.
Enable Monitor
Address: 31
OK
146
ESC
Step 8:
> Display safety note.
►
Confirm with [OK].
> Display of the address of the first found safety monitor.
►
Press [ ] or [ ] to scroll to the requested address of the safety
monitor.
IMPORTANT:
Select the same setting as with "ASIMON" in the safety