Operation
Set the diagnostic characteristics of the safety monitor
456
Slave List of
AS-i master 1
Safety Master 1
OK
130
ESC
Step 5:
AC1375: Menu screen not available.
►
Select safety master with [OK].
.
Safety Monitor
Read Monitor
Trigg.Slave
OK
141
ESC
Step 6:
►
Press [ ] to scroll to [Setup Monitor].
.
Safety Monitor
Disable Monitor
Setup Monitor
OK
141
ESC
Step 7:
►
Select [Setup Monitor] with [OK].
.
Monitor Settings
Sorted diag.
Unsorted diag.
OK
159
ESC
Step 8:
> Display of the current setting of the safety monitor (marked line =
active):
sorted = sorting by enable circuits,
unsorted = sorting by numbers of the safety devices.
►
Press [ or ] to scroll to the requested setting.
IMPORTANT:
Select the same setting as with "ASIMON" in the safety
monitor.
.
Monitor Settings
Sorted diag.
Unsorted diag.
OK
159
ESC
Step 9:
►
Confirm the setting with [OK].