2012-02-23
Operation
Set output values
472
Analogue value
AS-i 1 Slave 9
Channel: 2
Current: +0
Setup: +0
SET
155
ESC
Step 12:
> Current = analogue output channel current value.
> Setup = analogue output channel target value.
►
Press [ ] or [ ] to set the requested target value:
Brief pressing: step increment 1.
Long pressing: step increment 100.
.
Analogue value
AS-i 1 Slave 9
Channel: 2
Current: +0
Setup: +604
SET
155
ESC
Step 13:
> Setup = set target value.
►
Transmit the set target value to the outputs of the slaves by pressing
[SET].
.
Analogue value
AS-i 1 Slave 9
Channel: 2
Current: +604
Setup: +604
SET
155
ESC
Step 14:
> Value in "Current" adopts value from "Setup".
> Outputs on the slave are set accordingly.
> The value of set outputs remains unchanged until a new setup or a
new connection to the Profibus DP master changes the outputs again.
.
Analogue value
AS-i 1 Slave 9
Channel: 2
Current: +604
Setup: +0
SET
155
ESC
Step 15:
When the test has been finished:
►
Reset of the target value to "0" by pressing [ ]!
►
Transmit the set target value to the outputs of the slaves by pressing
[SET].