Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Set-up
Configuration of the slaves
121
9.1.2
Automatic individual addressing of slaves
5501
Now address the slaves. This is possible by means of the buttons and the text/graphics display on the
device. In the "Easy Startup" mode the device can address the slaves automatically in rising order if
the slaves are connected one after the other on the bus.
NOTE
However, this automatic process only works without problems if the slave to be connected has the
address 0!
If the slave has already been used in another system, it probably already has another address than 0.
In such a case, the device does not react to the connection of the new slave. This slave is not
automatically addressed.
Then
chapter Manual slave addressing (
→
page
Password level 1 required:
chapter Password setting (
→
page
[MENU] > [Slave Addresses] > [Easy Startup] > select master > connect slave > [ESC]
MENU
0
USER
Step 1:
►
Press [Menu].
Quick Setup
PLC Setup
Slave Lists
OK
1
ESC
Step 2:
►
Press [ ] to scroll to [Slave Addresses].