Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Set-up
Change slave parameter data
133
9.2
Change slave parameter data
5518
The parameter value "0Fh" is preset for the slaves.
Example
for a useful parameter change: Not connected analogue input channels generate a
peripheral fault of the module. By changing parameters you can block unused channels so that the
module does not trigger a peripheral fault.
Please note the corresponding remarks in the instructions of the modules.
Info
Password level 2 required:
chapter Password setting (
→
page
Changed values are not adopted in case of a wrong password level.
[MENU] > [Slave Setup] > select master > select slave > [Parameter Value] > change parameter data >
[SET]
MENU
0
USER
Step 1:
►
Press [Menu].
Quick Setup
PLC Setup
Slave Lists
OK
1
ESC
Step 2:
►
Press [ ] to scroll to [Slave Setup].
Fieldbus Setup
Slave Info
Slave Setup
OK
1
ESC
Step 3:
►
Select [Slave Setup] with [OK].
AC1375: continue with step 6.