Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Set-up
Parameter setting of the Profibus host
153
Analogue inputs/outputs
Analogue inputs......................................................................................................................... 154
Analogue outputs ...................................................................................................................... 155
5554
Example:
Siemens S7 with AS-i gateway:
The analogue inputs on the AS-i gateway are assigned to the host as bytes 256...287 (32 bytes = 16
words). The analogue inputs on the AS-i master are assigned to the host as bytes 256...271 (16 bytes
= 8 words).
The order of the shown analogue slaves can be explicitly defined via parameters in the Profibus
configuration.
►
To adapt the parameters, double-click on the gateway symbol.
►
Change to the tab [Parameter Setting] in the window which appears.
figure below: